Reference Manual
00809-0100-4811, Rev DA
Section 4: Basic Configuration/Start-Up
January 2015
Basic Configuration/Start-Up
Measurements below probe end
The Present Level=0... check-box controls how the level value is presented when the tank is
almost empty. By selecting this check- box, the Level is set equal to zero as long as the product
surface is below the probe.
If the check-box is not selected, the level value is equal to the difference between reference
gauge height R and probe length L when the product surface is below the probe (see Basic
configuration on page 62 for information on tank geometry).
4.6.11 Setup - Volume
The Volume tab allows you to configure the transmitter for volume calculations.
Figure 4-9. Setup Volume Tab
You can select one of the standard tank shapes or the strapping option. Select None if volume
calculation is not used at all.
Select one of the following options:
Vertical cylinder
Horizontal cylinder
Vertical bullet
Horizontal bullet
Sphere
Strap table
None
For further information, see Volume configuration on page 64.
Level = 0
Level = R - L