Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
C.11.6 ScadaPack
Figure C-13. Wiring Diagram for Connecting 3300 Modbus to SCADAPack 32
Table C-23. Parameter Values (in case of SCADAPack 32)
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 3300 Series Transmitter. In this case, register 1302 needs to have 31303 entered as
the address etc.
C.11.7 Kimray DACC 2000/3000
This table shows input types in Kimray IMI software and the corresponding value. The
communication port must be configured to use “Tank Levels” protocol.
Table C-24. Kimray Input Types and Corresponding Values
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type Floating Point
Input Register Base Number 30001
Kimray Inp type 3300 variable Format
Tank Level1 PV ddd.dd.alt. -dd.dd
Tank Level2 SV ddd.dd.alt -dd.dd
+ 8 to + 30 Vdc
(max. rating)
REF