Section 3: Installation
January 2015
Installation
3.5.5 Shortening the probe
Flexible twin/single lead
Note
The PTFE covered probes must not be cut in field.
Rigid single lead
1. Cut the single lead probe to the desired length.
2. Update the transmitter configuration to the new probe length, see “Probe length” on
page 70.
Note
The PTFE covered probes must not be cut in field.
1. Mark off the required probe length. Add
at least 1.6 in. (40 mm) to the required
probe length to be inserted into the
weight.
2. Loosen the Allen screws.
3. Slide the weight upwards as much as
needed in order to cut the probe.
4. Cut the probe. The minimum probe
length is 3.33 ft (1 m). If necessary,
remove a spacer to make room for the
weight.
5. Slide the weight down to the required
cable length.
6. Tighten the screws.
7. Update the transmitter configuration to
the new probe length, see “Probe length
on page 70.
If the weight was removed from the cables
when cutting, make sure that at least
1.6 in./40 mm of the cable is inserted when
the weight is replaced.
Allen
screws
Minimum:
1.6 in.
(40 mm)
Spacer
Cut